Problem:
What are the protocol settings for all of the types of panels on Comtool?
Solution:
3400 Version 3 - Half Duplex
Vigilon BS/3400 V3+ - Half Duplex
Vigilon EN54 - Full Duplex
Senator Advance - Half Duplex
Vigilon Compact (use Vigilon EN54) - Half Duplex
3400 and Vigilon BS panels can be set-up to Full Duplex but this would only be on large site and is not common.
If the domain has been changed on either a Vigilon Compact or Senator Advanced then Full Duplex will need to be used.