GentExpert Technical Forum FAQ

Here you can find answers to questions about how the board works. Use the links or search box below to find your way around.

3400 V3+

Problem
what is the minimum software for V3+

Solution
LCC, I/O and any LPC cards all must be at V3.30 or above

Comm tool version

The latest release of the commisioning tool is V1.21 Gent, V1.22 SMS

34000 devices

Problem
What is the minimum software I can use to run 34000 devices

Solution
BS: LCC, I/O and LPC cards need to be at v3.40 or above

EN: LCC, I/O and LPC cards need to be at v4.01 or above (so any EN panel)

S-cubed (S3) backwood compatable

problem
what is the minimum software to run the S3 backwood compatable sounder

solution
BS:
LCC v3.40
I/O v3.40
LPC v3.46
NW does not matter

EN:
LCC v4.01
I/O v4.01
LPC v4.01
NW does not matter

S-cubed (S3)

problem
what is the minimum software that will run S-cubed devices

Solution
BS:
LCC v3.70
I/O v3.72
LPC v 3.80 sounder only, v3.81 with strob
NW does not matter

EN:
LCC v4.10
I/O v4.05
LPC v 4.10 sounder only, v4.11 with strob
NW does not matter

S-Cubed (S3) sounders MKII

Problem
what is the minimum software I can use S3 MKII devices on

Solution
BS:
MCC v3.90 (note this must be an MCC card)
I/O v3.74
LPC v3.90
NW does not matter

EN:
MCC v4.30 (note this must be an MCC card)
I/O v 4.08
LPC v4.30
NW does not matter

S-quad (S4)

Problem
what si the minimum software I can use S4 devices on

Solution
BS:
(S4 devices can only be added to vigilon BS system)
MCC v3.90 (note this must be an MCC card)
I/O v3.74
LPC v3.90
NW does not matter

EN:
MCC v4.30 (note this must be an MCC card)
I/O v 4.08
LPC v4.30
NW does not matter

S4-34800, MCP

Problem
what is the minimum software I can use the S4-34800 MCP on

Solution
BS:
MCC v3.40
I/O v3.40
LPC v3.40
NW does not matter

EN:
MCC v4.01
I/O v 4.01
LPC v4.01
NW does not matter

vigilon voice interface

Problem
what is the minimum software I can use the vigilon voice interface on

Solution
BS:
MCC v3.90
I/O v3.40
LPC v3.90
NW does not matter

EN:
MCC v4.30
I/O v 4.01
LPC v4.30
NW does not matter

Orator 2

Problem
what is the minimum software I can use Orator on

Solution
BS:
MCC v3.65
I/O v3.40
LPC v3.47
NW does not matter

EN:
MCC v4.00
I/O v 4.00
LPC v4.00
NW does not matter

vigilon interface - medium Voltage

Problem
what is the minimum software I can use the S4-Interface medium voltage on

Solution
BS:
MCC v3.90
I/O v3.40
LPC v3.93
NW does not matter

EN:
MCC v4.31
I/O v 4.01
LPC v4.35
NW does not matter

Vigilon interface - Low voltage

Problem
what is the minimum software I can use the S4-interface low voltage on

Solution
BS:
MCC v3.94
I/O v3.40
LPC v3.93
NW does not matter

EN:
MCC v4.37
I/O v 4.01
LPC v4.35
NW does not matter

Compact VA

Problem
What is the minimum software required to run compact VA.

Solution
MCB v4.22
LPC v4.20